ION7550/7650

Picture
High performance meters for utility networks, mains or critical loads on HV/LV networks
Picture
The PowerLogic ION7550 and ION7650 each have a different feature set:
  • ION7550: revenue-class power and energy metering, event and min/max logging, historical logging (up to 800 channels), expandable memory, sag/swell monitoring, harmonics measurement, waveform capture at 256 samples/cycle, setpoints, digital and analog I/O, and Internet-enabled multi-port communications
  • ION7650: adds symmetrical components measurement, fast transient detection, waveform capture at 1024 samples/cycle, and power quality compliance monitoring.
View datasheet
View user manual
Contact us

ION7550/7650 Characteristics (some features are optional):

  • Panel-mount, large customizable LCD display, available without display
  • Multilingual support for English, French, Spanish and Russian. 12/24 hour clock support in multiple date/time formats.
  • 3-phase, 4-quadrant metering, class 0.2 accuracy (IEC, ANSI)
  • Voltage, current, neutral and ground current, power, frequency, power factor, demand, energy, and time-of-use metering
  • Instrument transformer correction, transformer/line loss compensation
  • IEC 61000-4-30 class A, IEEE 519/1159, EN50160, IEC 61000-4-7/4-15 power quality compliance monitoring
  • Up to four dedicated simultaneous IEC 61850 client connections through the Ethernet port. IEC 61850 is the Ethernet-based protocol designed for electrical substations.
  • Convention settings enable you to set certain parameters to either IEEE or IEC conventions. These settings affect the front panel display and harmonics calculations.
  • 1024 samples/cycle waveform capture, transient capture (20 μs @ 50 Hz), sag/swell monitoring, harmonics measurement (up to 63rd), symmetrical components
  • Disturbance direction detection to indicate whether a disturbance originated upstream or downstream from the meter
  • Setpoint learning to automatically learn what constitutes a sag, swell, transient or high and low setpoint
  • Sequence-of-events, coincident minimum/maximum, historical trends, and high-speed snapshot recording, 1 ms resolution timestamping, GPS time synchronization
  • 4 analog inputs, 4 analog outputs, 16 digital status/counter inputs, 7 digital control/pulse outputs
  • 65 setpoints for alarms and control, 1/2 cycle response, multi-condition, call out on alarm
  • 5 communication ports: Ethernet, modem, RS-232/485, RS-485, front panel optical
  • 100Base–TX and 100Base–FX for faster Ethernet communication
  • Protocols: Modbus RTU slave/master, Modbus TCP, DNP 3.0, MV-90
  • Ethernet and modem gateways to 31 devices on RS-485 port
  • On-board web server, email for alarms and data
Picture

Benefits

The PowerLogic ION7650/ION7550 meters help you:
  • reduce energy and operations costs
  • improve power quality, reliability and uptime
  • optimize equipment use for optimal management of your electrical installation and greater productivity.

Applications

  • Analysis of efficiency, losses and capacity
  • Bill verification, cost allocation and sub-metering
  • Power quality compliance monitoring
  • Problem notification and diagnosis
  • Demand or power factor management
  • Control of loads, generators or other equipment 
Learn more about DDD

Resources

Technical Datasheet
Download Datasheet
Brochure
Download Brochure
Product Selector
View

Need More Info?

Contact Us

Delivering Intelligent Data

Contact Us

+64 3 343 9150

sales@quasar.co.nz

Unit 9, 1 Stark Drive, Wigram
Christchurch, New Zealand

Site Search

Products

Power Monitoring Expert
Power SCADA
Load Control
Power Metering Hardware
ADMS & HMI

Sector Solutions

Electricity Sector
Primary Sector & Manufacturing
Services Sector
Government, Education & Health
Commercial Buildings
Contractors & Consultants

Case Studies

Datasheets & Guides

About Us

Meet the Team
Our History
EcoXpert
Careers

Subscribe to Email Updates

Subscribe

Read Our Blog

© 2021 Quasar Systems Ltd
Terms and Conditions of Sale
Privacy Policy
Terms of Use
  • Products
  • Sector Solutions
  • Case Studies
  • Datasheets & Guides
  • Store
  • About Us
  • Contact Us